DP121 Low Water Limiter Probe
Application and function
In conjunction with the self-monitoring low water level limiter DLL, the low water limiter probe is a limiter with safety function in accordance with the EU Directive 2014/68/EU (PED) (special design according to Water Level 100).Conformity (CE marking) is certified in accordance with Annex III, Modules B+D (Category IV); notified body NB 0035.
Regulations applied: corresponding DIN EN standards.
Technical basic equipment
Mechanical connection |
G ½ |
|
Power connection |
CAN-Bus according to DIN ISO 11898 Electrical connector |
|
Materials |
Electrode housing |
stainless steel |
Electrode rod |
stainless steel |
|
Electrode extension |
stainless steel |
|
Insulator |
Ceramic |
|
Plug / socket |
PA66, zinc diecasting |
Electrical data
Responsiveness >0.5µS/cm at 25°C
Power supply 24V
Power consumption 0.6W
Data exchange CAN-Bus in accordance with DIN ISO 11898, CANopen protocol
Electrical connection CAN-Bus in accordance with DIN ISO 11898
Protection class IP65 in accordance with DIN EN 60529
Allowable ambient temperature: 0°C to 85°C
Self-test every 3sec