Open questions?

 +49 2501 92424 0

Float switch type BA14

80 bar

Application and function

The float switch can be used as water level limiter for steam generators as per TRD 401, 402 or 602.

The product corresponds to the EU 2014/68/EU module B and has the CE-mark no. 0035 of the notified body. Applied standards as per EN 13445 / EN 12952 / EN 12953 / AD 2000 or ASME-Boiler.

Technical basic equipment

  • Material according to DIN or ASME
  • Protection as per DIN VDE 0470: IP54
  • Process connection: flanges as per DIN or ANSI
  • Magnetic switch type M130-K (D-07-D-16324-0)
  • Cable gland according to DIN EN 50262: M20x1,5
  • Drain plug G ½

Available (optional) versions

  • Protection as per DIN VDE 0470: IP65
  • Process connection: welding end, Socket Welding
  • Level indication (signal lamps), data sheet D-07-D-16323-0
  • Ventilation screw
  • Drain valve AV500 or 520

Accessories

Level indication

Signal lamps for water level indication