DP411 Level Probe
Application and function
This 4-rod level probe combines 2 functions.
With a DLL low water level limiter one rod forms a limiter with safety function in accordance with the EC Directive 2014/68/EC (PED). Conformity (CE marking) is certified in accordance with Annex III, Modules B+D (Category IV); notified body NB 0035.
In conjunction with the DCU discontinuous water level controller the other 3 rods form a 2-point water level regulating system with LW or HW signalling.
Here the product meets EU Directive 2014/68/EU.
Regulations applied: corresponding DIN EN standards.
Technical basic equipment
Mechanical connection |
G ½ |
|
Power connection |
CAN-Bus in accordance with DIN ISO 11898 Electrical connector |
|
Materials |
Electrode housing |
stainless steel |
Electrode rod |
stainless steel |
|
Electrode extension |
stainless steel |
|
Insulator |
PTFE |
|
Plug / socket |
PA66, zinc diecasting |
Electrical data
Responsiveness >0.5µS/cm at 25°C
Power supply 24V
Power consumption 0.6W
Data exchange CAN-Bus in accordance with DIN ISO 11898, CANopen protocol
Electrical connection CAN-Bus in accordance with DIN ISO 11898
Protection class IP65 in accordance with DIN EN 60529
Allowable ambient temperature: 0°C to 85°C
Self-test every 3sec