DP313 3-Rod Level Probe
Application and function
In conjunction with the DCU discontinuous water level controller, the 3-rod level probe forms a 2-point water level control system with LW or HW signalling.
The product meets EU Directive 2014/68/EU (PED).
Regulations applied: corresponding DIN EN standards.
Technical basic equipment
Mechanical connection |
G 1" |
|
Power connection |
CAN-Bus according to DIN ISO 11898 Electrical connector |
|
Materials |
Electrode housing |
stainless steel |
Electrode rod |
stainless steel |
|
Electrode extension |
stainless steel |
|
Insulator |
PTFE |
|
Plug / socket |
PA66, zinc diecasting |
Electrical data
Responsiveness >0.5µS/cm at 25°C
Power supply 24V
Power consumption 0.6W
Data exchange CAN-Bus in accordance with DIN ISO 11898, CANopen protocol
Electrical connection CAN-Bus in accordance with DIN ISO 11898
Protection class IP65 in accordance with DIN EN 60529
Allowable ambient temperature: 0°C to 85°C
Self-test every 3sec