Level limiter LW LMC2

Application and function

In conjunction with the IGEMA level probe, the level limiter LMC2 is a self-testing level limiter (LW).

Regulations applied:
AD2000, EN61508-1/-2/-3, EN61326-1, EN61010-1

Due to a self-test, the limiter ensures the safety function. Thus it can be implemented in systems with safety requirements up to SIL 3.

Function LMC2

The level limiter (LW) LMC2 works in conjunction with the IGEMA level probes on the basis of the conductive fill level method of measurement, whereby the electric conductivity of the liquid is used. The conductivity of the medium is measured in µS/cm. For the secure functioning of this method of measurement a minimum conductivity of the substance to be measured is required.

The conductive method of measurement shows two results: electrode submerged or electrode uncovered, or switch point reached or not reached. Before installation the electrode must be adjusted to the length at which the switching procedure is to be executed, e.g. for switching off burner and interrupting the safety circuit.

LEDs in different colors show the state of the system. This assists the troubleshooting.

If all conditions for correct operation are met, the safety circuit for the steam generator is enabled (burner can switch on).

In the LMC2 the current across the electrical contacts of the safety circuit is limited by a 4A fuse. Thus jamming of the contacts is avoided.

In the case of a low liquid level, the output (relay) of the safety circuit is deactivated after a total adjustable delay of 4s, 8s, 12s or 16s, thus the burner is cut-off. The preset delay time is 4s.

A latching is not implemented in to the LMC2. It has to be installed by the operator.

The self-test ensures the functionality, thus a test button is not necessary.

Probes

Probe PS TS Connection Electrode length
EL041 32bar 239°C G 1/2" 125mm - 1700mm
EL041-B 32bar 239°C G 3/4" 125mm - 1700mm
EL241 200bar 367°C G 1/2" 150mm - 1700mm

Technical basic equipment

  • LMC2 is delivered in a plastic plug-in housing for installation in control panels
  • Fixation on standard rail 35 mm according to DIN EN 50022 or directly screwed to chassis plate